NO. 712
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Trowel |
Roofer's Knife |
Application
NOTE: Prior to application, consult
the waterproofing manufacturer to determine whether the polyethylene film
facing on one side, or the asphalt-impregnated reinforced mat on the other
side of SEALTIGHT PROTECTION COURSE is approved as "compatible"
to the specific waterproofing product being protected.
SEALTIGHT PROTECTION COURSE is installed to form a continuous protective
layer over the membrane waterproofing. The sheets can be easily cut with
a roofer's knife for fitting at protrusions.
SURFACE CONDITION: The waterproofing membrane must be free of sharp projections,
dirt and dust. If water testing is desired, it should be made prior to
placing the protection course. Note: Protection course should be applied
at the end of each day's waterproofing to both horizontal and vertical
surfaces.
HORIZONTAL SURFACES: PROTECTION COURSE should be installed over the waterproofing
membrane as soon as permissible by the membrane applicator or manufacturer.
PROTECTION COURSE sheets should be butted together and cut to fit all
intersecting surfaces and protrusions. If desired, joints may be covered
with SEALTIGHT Detail Strip or roofer's glass reinforced tape embedded
in hot asphalt as a secondary waterproofing system. (See Point 2 under
Limitations/Precautions).
VERTICAL SURFACES: For dampproofed and/or waterproofed vertical walls
to receive backfill, the PROTECTION COURSE should be butt-jointed and,
if necessary, temporarily held in place while backfilling.
BACKFILLING: Backfilling against vertical walls should be done immediately
using care and caution to avoid damaging the waterproofing application.
Backfill material should not be dropped against the PROTECTION COURSE
in such a manner that it could drag the sheet down as the backfill drops.
For horizontal applications, the waterproofing and PROTECTION COURSE should
be installed just prior to the installation of the wearing surface.
Packaging
4' x 8' (1.22m x 2.44m) panels
Limitations / Precautions
1. Where PROTECTION COURSE is adhered to waterproofing membrane,
use the adhesive recommended by the membrane manufacturer.
2. Where taped joints are desired with tape set in hot asphalt, consult
membrane manufacturer.
3. PROTECTION COURSE is shipped on pallets with the polyethylene anti-stick
sheet on the top or exposed side. PROTECTION COURSE should be stored on
the pallets and placed on a level surface.
4. CAUTION: Do not apply the Protection Course over liquid applied waterproofing
membranes containing volatile solvents until all of the solvent has evaporated.
Consult membrane manufacturer for specific application details prior to
placing the Protection Course. Read and follow application information
and precautions.
| Classes | Type 1 | Type 2 | Type 3 | |
| Puncture Strength |
|
222 N (50 lbf) minimum |
312 N (70 lbf) minimum |
365 N (82 lbf) minimum |
| Thickness |
|
1.3 to 1.8mm (0.050 to 0.070 in.) |
2.4 to 3.9mm (0.095 to 0.155 in.) |
5.6 to 7.1mm (0.22 to 0.28 in.) |
| Water Absorption |
|
10% maximum | 10% maximum | 10% maximum |
| Asphalt, % by weight |
|
65% minimum | 65% minimum | 65% minimum |
| Asphalt, % by weight |
|
40% minimum | 40% minimum | 40% minimum |
| Resistance to Decay |
|
All Types - Meets puncture requirements after completion of test | ||
| TYPE PC-1 Light Duty PC-2 Standard Duty PC-3 Heavy Duty |
THICKNESS* 62.5 mil-1/16' (1.59mm) 125 mil-1/8' (3.18mm) 250 mil-1/4' (6.35mm) |
WIDTH 4' (1.22m) 4' (1.22m) 4'(1.22m) |
LENGTH 8' (2.44m) 8' (2.44m) 8' (2.44m) |
| *Nominal |
This material last updated December, 2001.