NO. 714
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| PROPERTY | TYPICAL VALUE | TEST METHOD |
| Color Carrier Film | White | |
| Polymeric Membrane | Black | |
| Thickness Carrier Film | 4 mils | |
| Polymeric Membrane | 56 mils | |
| Tensile Strength Carrier Film | 5,900 psi min. (40.71MPa) | ASTM D 412 (Die C) |
| Polymeric Membrane | 590 psi min. (4.07MPa) | |
| Elongation Polymeric Membrane |
455% min. | ASTM D 412 (Die C) |
| Peel Adhesion Dry | 7-11 lb./in. (125-196 g/mm) width, min. | Footnote ¹ |
| Peel Adhesion Wet | 7-12 lb./in. (125-214 g/mm) width, min. | |
| Pliability 180º Bend 1" (25.4mm) Mandrel @ -25ºF (-32ºC) |
Unaffected (5.72/10g/PaSM²) |
ASTM D 146 |
| Water Vapor Transmission | .05 gr./sq.ft./hr. | ASTM E 96 (Method B) |
| Water Absorption | 0.1%, 72 hrs. max. | ASTM D 570 (M) |
| Resistance to Hydrostatic Head | Equiv. to 240 ft. (73.1m) of water | Footnote ² |
| Puncture Resistance | 67 lbs. | ASTM E154 |
| Exposure to Fungi | Pass, 16 weeks | Soil Test |
| ¹ 90% peel after 7 days at 70ºF (-21ºC) plus 7 days at 120ºF (49ºC) plus 7 days at 70ºF (-21ºC) (Dry) (Wet). | ||
| ² Membrane placed over a porous base in a test cell and edges sealed. Water was placed over test specimen. Cell fastened and sealed and placed under 105 psi (.73 Mpa) (approx. 240 foot (73.1m) water head) pressure for 24 hours. Test specimen did not show any water to permeate the membrane. | ||
|
Knife |
Roller |
Caulking Gun |
Manual Sprayer |
Paint Roller |
Application
SURFACE PREPARATION...Concrete
should be cured at least 72 hours, be clean, dry, smooth and free of voids.
Repair spalled areas; fill all voids and remove all sharp protrusions.
*TEMPERATURE...Apply in dry, fair weather when the air and surface
temperatures are above 40ºF (4ºC). Do not apply to frozen concrete.
*MEL-ROL WINTERGRADE
(W/G)...a low temperature membrane can be used when air and surface temperatures
are between 20ºF (-7ºC) and 60ºF (16ºC).
PRIME...Prior to application, prime all surfaces to be covered in one
working day with applicable MEL-PRIME Primer. Uncovered, primed surfaces
must be reprimed the next day. Follow all instructions and precautions
shown on primer containers.
FOOTING DETAILS...Use SEALTIGHT Detail Strips for impaction sheet coverage.
First, fold strips lengthwise and then cut at the fold. Material is then
ready to install as 4-1/2" (114.3mm) strips on either side of the
rebar. Any excess can be turned down the face of the footing. Next, fill
the void around rebars in the keyway with SEALTIGHT Catalytic Bonding
Asphalt. Pour the walls. Install a SEALTIGHT Detail Strip horizontally
along the wall where it meets the footing, placing half the material up
the wall and the other half onto the footing. Extend the material 4-1/2"
(114.3mm) beyond outside corners. Slit extended portion of detail strip
lengthwise. Place the horizontal flap out onto the footing and bend the
vertical flap around the wall (See Diagram A). Repeat this procedure in
the opposite direction as shown in Diagram B.
|
|
|
HORIZONTAL APPLICATIONS...Position the MEL-ROL Membrane from low to high point so all laps will shed water. Stagger end laps and overlap all seams at least 2.5" (63.5mm). Apply a double-thickness of the MEL-ROL Membrane over construction, control and expansion joints and over cracks greater than 1/16" (1.59mm) wide.
VERTICAL WALL APPLICATION: Apply MEL-ROL Membrane vertically in lengths approximately 8' (2.44m) long over the top of the horizontal Detail Strips at the footing. Overlap all seams at least 2.5" (63.5mm). Tightly butt edges of membrane and apply SEALTIGHT Pointing Mastic in corner applications (See Diagram C).
To the top terminations, apply SEALTIGHT Pointing
Mastic at least 1/8" (3.18mm) thick and 1" (25.4mm) wide. As
an option; SEALTIGHT Termination Bars may be used to mechanically fasten
the membrane. Masonry walls must be parge-coated with an asphaltic foundation
coating or a cementitious material before applying MEL-ROL.
HAND-RUB AND ROLL PRESS: Once positioned, immediately hand-rub MEL-ROL
Membrane firmly to the surface and then pressure roll the complete surface
to assure positive adhesion.
INSIDE CORNERS: Before MEL-ROL is applied, place a
vertical SEALTIGHT Detail Strip on inside corners extending the material
4-1/2" (114.3mm) beyond each side of the corner (See Diagram D).
Terminate at the footing and finish the corner with SEALTIGHT Pointing
Mastic.
|
|
|
|
|
![]() |
INSPECT AND REPAIR...A thorough inspection should
be made before covering and all necessary repairs made immediately. Tears
and inadequate overlaps should be covered with MEL-ROL Membrane. Slit
fishmouths and patch. Seal edges of all patches with SEALTIGHT Pointing
Mastic. Where applicable, horizontal applications can be flood-tested
for 24 hours. All leaks should be marked and repaired when membrane dries.
PROTECT THE MEMBRANE...on all vertical and horizontal installations with
the immediate application of SEALTIGHT Protection Course, if no drainage
system is used, or MEL-DRAIN. (Refer to Data Sheets No. 712 and 719 for
application instructions.) Use SEALTIGHT Pointing Mastic as an adhesive.
Backfilling should be done immediately using care and caution to avoid
damaging the waterproofing application.
Precautions
Avoid the use of products which
contain tars, solvents, pitches, polysulfide polymers, or PVC materials
that may come into contact with MEL-ROL. Read and follow application information,
precautions and Material Safety Data information.
Accessories
SEALTIGHT MEL-PRIME WATER-BASE PRIMER:
Prepares concrete surfaces for MEL-ROL Membrane application. Arrives ready-to-use.
Requires no additional mixing. MEL-PRIME W/B emits no unpleasant odors
and works with all SEALTIGHT Waterproofing Membranes. Applied easily with
manual sprayer or roller. VOC-compliant. MEL-PRIME W/B is for use at temperatures
of 40ºF (4ºC) and up. (Refer to Data Sheet No. 752).
| Coverage: 250 to 350 sq.ft./gal.
(6.14 to 8.59 sq.m/L) Packaging: 1 Gallon (3.79 Liter) Units (4 units per carton) and 5 Gallon (18.93 Liter) Pails |
SEALTIGHT MEL-PRIME SOLVENT-BASE or VOC COMPLIANT
SOLVENT-BASE PRIMERS...These primers are for use at temperatures of 25ºF
(-4ºC) and above. (Refer to Data Sheet Nos. 751 and 7100-542).
| Coverage: 250-350 sq.ft./gal. (6.14
to 8.59 sq.m/L) Packaging: 5 gallon (18.93 liter) Pails |
SEALTIGHT MEL-ROL LIQUID MEMBRANE...A two-component
material used as a flashing, to form fillets at corners and at protrusions.
May be used as a substitute for the SEALTIGHT Pointing Mastic. (Refer
to Data Sheet No. 741).
| Coverage: As a fillet, approximately
135 lineal feet per gallon (10.87 meters per liter) Packaging: 1 gallon (3.79 Liter) units, 4 Units per carton. |
SEALTIGHT POINTING MASTIC...Used for sealing top edge
terminations on SEALTIGHT Detail Strips and Membrane. (Refer to Data Sheet
No. 740).
| Coverage: 1/8" x 1" x
200 ft./gal. (3.18mm x 25.4mm x 16.10ml) Packaging: 5 Gallon (18.93 Liter) Pails or 29 Oz. (857.65ml) Cartridges, 12/ctn. |
SEALTIGHT CATALYTIC BONDING ASPHALT...Easy-to-apply
one-component material for sealing around rebar.
| Coverage: 5 gal./1,000 sq.ft./gal.
(4.9 sq.m/L) Packaging: 5 gallon (18.93 Liter) Pails |
SEALTIGHT DETAIL STRIP: Convenient, easy-to-use detail
strips provide an economical and effective method for sealing vertical
and horizontal butt-joints i.e. inside or outside corners and where walls
and footings meet.
Packaging: 9" x 50' (.23 x 15.24m) roll, 4 rolls per carton.
| Packaging: 9" x 50' (.23 x 15.24M) toll. 4 rolls per carton |
SEALTIGHT PROTECTION COURSE: Use SEALTIGHT Protection Course for vertical and horizontal applications. Adhere with the SEALTIGHT POINTING MASTIC. Size...4' x 8' (1.22 x 2.44m) panels (Refer to Data Sheet No. 712).
SEALTIGHT MEL-DRAIN Rolled Matrix Drainage System...A dimple-raised molded polystyrene fabric designed to provide high flow capacity to reduce hydrostatic pressure build-up around waterproofing and vaporproofing membranes. Choice of drain-types available for vertical, horizontal and site applications. MEL-DRAIN is part of a complete MEADOWS Moisture Protection System. )Refer to Data Sheet No. 719).
Maintain Energy Efficiency
SEALTIGHT Products aid in the integrity
of other structural systems such as insulation. Because wet insulating
materials lose much of their R factor performance characteristics, this
reduces the energy efficiency of the structure. SEALTIGHT Products applied
for thermal and moisture protection help prevent moisture or vapor penetration
into the other systems. These products play a key role in maintaining
the structure's energy efficiency.
This material last updated June, 2002.
| Div. 07130 |
|
|