Home
Export for Manufacturers Supplying Distributors Business Opportunities Logistics
Home
Company Profile
Products
Affiliated Companies
Contact Us
search

 Div. 03600 Meadows  
U.S. Spec. Product Data


Guide Spec. No. 380

588™ PRECISION GROUT

NON-SHRINK, NON-FERROUS, NON-GASEOUS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Surface preparation.

B. Grout.

1.02 REFERENCES

A. Corps of Engineers Spec. CRD-C-621.
B. ASTM C 1107.
C. USDA Accepted.

SPEC NOTE: Remainder of Part 1 as applicable to specific project to be developed by specifier.

PART 2 PRODUCTS

2.01 ACCEPTABLE MANUFACTURER

A. W. R. MEADOWS, INC.
Nine Locations

2.02 MATERIALS

SPEC NOTE: SEALTIGHT 588 PRECISION GROUT is a Portland Cement-base product. It is non-corrosive, non-gaseous and provides high density, high initial and ultimate flexural and compressive strengths.

SEALTIGHT 588 PRECISION GROUT is suggested for precision grouting of machinery bases, generators, rolling mills, punch presses, compressors, etc.; structural grouting of precast columns, steel columns, crane rails, precast beams, etc; anchoring of guard rails, sign posts, bridge seats, anchor bolts, guide wires, dowels, etc.

A. Grout: pre-mixed, Portland Cement-base product that is non-shrink, non-ferrous and non-gaseous. Grout to be non-corrosive, meeting Corps of Engineers specification CRD-C 621, with a minimum strength at 28 days of 10,792 psi (74.5 MPa) when tested with a minimum flow (plastic) mix, SEALTIGHT 588 PRECISION GROUT, manufactured by W. R. MEADOWS, INC.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify substrate conditions under provisions of Section [ ].

3.02 PREPARATION

A. Perform grouting to established concreting procedures according to ACI recommendations. Clean all grout contact surfaces of oil, grease, scale and other loose and deleterious substances. Chip out unsound concrete, leaving surface level but rough.

B. Saturate grouting area with water 12-24 hours prior to grouting. Remove all excess water before placing grout.

3.03 INSTALLATION

A. Observe application information and precautions stated in manufacturer's literature.

B. Pouring: Forming must provide for rapid continuous grout placement. For pouring, allow a minimum clearance of 3 inches (76.2mm) for entry and 6 inches (152.4mm) minimum grout "head".

C. Venting: Forming must provide for venting to avoid air entrapment. Do not make close fitting forms, allow 1/2 inch (12.7mm) clearance and 1 inch (25.4mm) for "head".

D. Mix, place and cure grout in accordance to manufacturer's written instructions.

3.04 PROTECTION OF FINISHED WORK

A. Protect finished Work under provisions of Section [01500].

END OF SECTION
Top

Home I Co.Profile I Products I Affiliated Co's I Contact I Search I Export for Manufactr's I Supply Distributors I Bus. Opps I Logistics

 


CMI provides international sales for North American based construction materials manufacturers in the worldwide markets. CMI, construction materials international, building material, ceilings, manufacturer, construction, residential, commercial, roofing insulation, metal building products, roofing system, insulation, siding, GAF, W. R. Meadows, DOW, Rock-Tenn Company, International Specialty Products, ISP, Concrete Chemicals, Joint Sealant, Joint Filler, Waterproofing, Concrete Repair and Restoration, Roofing Granules, laminated paperboard, steep slope, low slope, coatings, cements, thermax.