SECTION 07130
WATERPROOFING MEMBRANE SYSTEM
| Specifier Notes: W.R. Meadows
SEALTIGHT MEL-ROL Waterproofing System is a roll-type membrane for
use in providing waterproofing protection against damaging moisture
migration and the infiltration of free water. |
PART 1 GENERAL
1.1 SECTION INCLUDES
- A. Rolled, self-adhering waterproofing membrane
system.
1.2 RELATED SECTIONS
| Specifier Notes: Edit the list
of related sections as required for the project. List other sections
dealing with work directly related to this section. |
- A. Section 07100 - Dampproofing and Waterproofing.
1.3 REFERENCES
- A. American Railway Engineering & Maintenance
of Way Association (AREMA) Specification Chapter 29 - Waterproofing.
B. ASTM D 146 - Sampling and Testing Bitumen-Saturated Felts and Fabrics
Used in Roofing and Waterproofing.
C. ASTM D 412 - Vulcanized Rubber and Thermoplastic Rubbers and Thermoplastic
Elastomers-Tension.
D. ASTM D 570 - Water Absorption of Plastics.
E. ASTM E 96 - Water Vapor Transmission of Materials.
F. ASTM E 154 - Water Vapor Retarders Used in Contact with Earth Under
Concrete Slabs, on Walls, or as Ground Cover.
1.4 SUBMITTALS
- A. Comply with Section 01330 - Submittal Procedures.
B. Submit manufacturer's product data and application instructions.
1.5 DELIVERY, STORAGE, AND HANDLING
- A. Delivery: Deliver materials to site in manufacturer's
original, unopened containers and packaging, with labels clearly identifying
product name and manufacturer.
B. Storage:
-
-
- 1. Store materials in a clean dry area in accordance
with manufacturer's instructions.
2. Store membrane cartons on pallets.
3. Do not store at temperatures above 90 degrees F (32 degrees C)
for extended periods.
4. Keep away from sparks and flames.
5. Completely cover when stored outside. Protect from rain.
Ê
- C. Handling: Protect materials during handling
and application to prevent damage or contamination.
1.6 ENVIRONMENTAL REQUIREMENTS
- A. Do not apply membrane when air or surface temperatures
are below 25 degrees F (-4 degrees C).
B. Do not apply to frozen concrete.
PART 2 PRODUCTS
2.1 MANUFACTURER
- A. W.R. Meadows, Inc., PO Box 338, Hampshire, Illinois
60140-0338. (800) 342-5976. (847) 683-4500. Fax (847) 683-4544. Web
Site www.wrmeadows.com.
2.2 MATERIALS
- A. Rolled, Self-Adhering Waterproofing Membrane:
SEALTIGHT MEL-ROL Waterproofing System.
1. Description: Polymeric waterproofing membrane protected by release
paper on cross-laminated polyethylene carrier film with exposed
polymeric membrane strips on both sides protected by pull-off release
strips.
2. Compliance: AREMA Specification Chapter 29 - Waterproofing.
3. Thickness:
a. Carrier Film: 4 mils.
b. Polymeric Membrane: 56 mils.
4. Tensile Strength, ASTM D 412, Die C:
a. Carrier Film: 5,900 psi (40.71 MPa) minimum.
b. Polymeric Membrane: 590 psi (4.07 MPa) minimum.
-
- 5. Elongation, ASTM D 412, Die C:
a. Polymeric Membrane: 455 percent minimum.
-
- 6. Peel Adhesion:
a. Dry: 7 to 11 pounds/inch (125 to 196 g/mm) width, minimum.
b. Wet: 7 to 12 pounds/inch (125 to 214 g/mm) width, minimum.
-
- 7. Pliability, ASTM D 146:
a. 180 Degree Bend: Unaffected.
b. 1 Inch (25.4 mm) Mandrel at -25 degrees F (-32 degrees C):
5.72 x 10-9 g/Pa-s-m².
8. Water Vapor Transmission, ASTM E 96, Method B: 0.05 grains/square
foot/hour.
-
- 9. Water Absorption, ASTM D 570: 0.1 percent,
72 hours maximum.
10. Resistance to Hydrostatic Head: Equivalent to 150 feet (45.72
m) of water.
11. Puncture Resistance, ASTM E 154: 67 pounds.
12. Exposure to Fungi, Soil Test: Pass, 16 weeks.
13. Color:
a. Carrier Film: White.
b. Polymeric Membrane: Black.
2.3 ACCESSORIES
- A. Primer:
-
-
- 1. Temperatures Above 40 Degrees F (4 Degrees
C): SEALTIGHT MEL-PRIME WATER-BASE PRIMER.
2. Temperatures Above 25 Degrees F (-4 Degrees C): SEALTIGHT MEL-PRIME
VOC COMPLIANT SOLVENT-BASE PRIMER or STANDARD SOLVENT-BASE PRIMER.
Ê
- B. Flashing: SEALTIGHT LIQUID MEMBRANE.
C. Pointing Mastic: SEALTIGHT POINTING MASTIC.
D. Bonding Asphalt: SEALTIGHT CATALYTIC BONDING ASPHALT.
E. Joint Tape: SEALTIGHT DETAIL STRIP.
F. Waterproofing Protection Course: SEALTIGHT PROTECTION COURSE.
G. Rolled Matrix Drainage System: SEALTIGHT MEL-DRAIN DB.
PART 3 EXECUTION
3.1 EXAMINATION
- A. Examine surfaces to receive waterproofing membrane
system. Notify Architect if surfaces are not acceptable. Do not begin
surface preparation or application until unacceptable conditions have
been corrected.
3.2 SURFACE PREPARATION
- A. Prepare surfaces in accordance with manufacturer's
instructions.
B. Cure concrete a minimum of 72 hours.
C. Ensure concrete is clean, dry, smooth, and free of voids.
D. Remove sharp protrusions and repair surface defects.
3.3 APPLICATION
- A. Apply waterproofing membrane system in accordance
with manufacturer's instructions.
B. Ensure accessory materials are compatible with membrane and approved
by membrane manufacturer.
C. Prime surfaces to be covered in 1 day with applicable primer. Reprime
uncovered surfaces next day.
D. Inspect membrane before covering and repair as necessary. Cover tears
and inadequate overlaps with membrane. Seal edges of patches with pointing
mastic.
E. Perform flood testing of horizontal applications, as required. Mark
leaks and repair when membrane dries.
F. Avoid use of products which contain tars, solvents, pitches, polysulfide
polymers, or PVC materials that may come into contact with waterproofing
membrane system.
3.4 PROTECTION
- A. Protect membrane on vertical and horizontal
applications with immediate application of waterproofing protection
course, if no drainage system is used, or rolled matrix drainage system.
Use pointing mastic as an adhesive.
B. Backfill immediately using care to avoid damaging waterproofing membrane
system.
END OF SECTION
|